Improvements in the cooling capacity and the COP of a transcritical CO2 refrigeration plant operating with a thermoelectric subcooling system
作者: Astrain, D.1,2; Merino, A.1; Catalan, L.1,2; Aranguren, P.1,2; Araiz, M.1,2; Sanchez, D.3; Cabello, R.3; Llopis, R.3
通讯作者: Astrain, D.
刊名: APPLIED THERMAL ENGINEERING
ISSN: 1359-4311
出版年: 2019
卷: 155, 页码:110-122
语种: 英语
英文关键词: CO2 ; Subcooling ; R744 ; Thermoelectricity ; Transcritical ; COP ; Computational model
WOS关键词: VAPOR COMPRESSION ; 2-PHASE EJECTOR ; DESIGN ; COOLER ; THERMOSIPHONS ; PERFORMANCE ; PELTIER ; ENERGY ; WATER ; CYCLE
WOS学科分类: Thermodynamics ; Energy & Fuels ; Engineering, Mechanical ; Mechanics
WOS研究方向: Thermodynamics ; Energy & Fuels ; Engineering ; Mechanics
英文摘要:

Restrictive environmental regulations are driving the use of CO2 as working fluid in commercial vapour compression plants due to its ultra-low global warming potential (GWP(100) = 1) and its natural condition. However, at high ambient temperatures transcritical operating conditions are commonly achieved causing low energy efficiencies in refrigeration facilities. To solve this issue, several improvements have been implemented, especially in large centralized plants where ejectors, parallel compressors or subcooler systems, among others, are frequently used. Despite their good results, these measures are not suitable for small-capacity systems due mainly to the cost and the complexity of the system.


Accordingly, this work presents a new subcooling system equipped with thermoelectric modules (TESC), which thanks to its simplicity, low cost and easy control, results very suitable for medium and small capacity plants. The developed methodology finds the gas-cooler pressure and the electric voltage supplied to the TESC system that maximizes the overall COP of the plant taking into account the ambient temperature, the number of thermoelectric modules used and the thermal resistance of the heat exchangers included in the TESC. The obtained results reveal that, with 20 thermoelectric modules, an improvement of 20% in terms of COP and of 25.6% regarding the cooling capacity can be obtained compared to the base cycle of CO2 of a small cooling plant refrigerated by air. Compared to a cycle that uses an internal heat exchanger IHX, the improvements reach 12.2% and 19.5% respectively.


Citation statistics:
资源类型: 期刊论文
标识符: http://119.78.100.158/handle/2HF3EXSE/140178
Appears in Collections:过去全球变化的重建

Files in This Item:

There are no files associated with this item.


作者单位: 1.Univ Publ Navarra, Engn Dept, Campus Arrosadia S-N, Pamplona 31006, Spain
2.Smart Cities Inst, Pamplona 31006, Spain
3.Jaume I Univ, Dept Mech Engn & Construct, Campus Riu Sec S-N, Castellon de La Plana 12071, Spain

Recommended Citation:
Astrain, D.,Merino, A.,Catalan, L.,et al. Improvements in the cooling capacity and the COP of a transcritical CO2 refrigeration plant operating with a thermoelectric subcooling system[J]. APPLIED THERMAL ENGINEERING,2019-01-01,155:110-122
Service
Recommend this item
Sava as my favorate item
Show this item's statistics
Export Endnote File
Google Scholar
Similar articles in Google Scholar
[Astrain, D.]'s Articles
[Merino, A.]'s Articles
[Catalan, L.]'s Articles
百度学术
Similar articles in Baidu Scholar
[Astrain, D.]'s Articles
[Merino, A.]'s Articles
[Catalan, L.]'s Articles
CSDL cross search
Similar articles in CSDL Cross Search
[Astrain, D.]‘s Articles
[Merino, A.]‘s Articles
[Catalan, L.]‘s Articles
Related Copyright Policies
Null
收藏/分享
所有评论 (0)
暂无评论
 

Items in IR are protected by copyright, with all rights reserved, unless otherwise indicated.